Permit: T07PL01734

Parcel: 116150010

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/18/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER
10/11/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1 FOOT OF COVER REQUIRED, LINE NOT DEEP ENOUGH
SHADE W/CLEAN FILL, NO ROCKS
GALV AT COPPER CONNECTION NOT ALLOWED
VACUUM BREAKERS REQUIRED AT ALL HOSE BIBS
PRESSURE VACUUM BREAKER REQUIRED FOR IRRIGATION
CONTROLS WITH VALVES DN STREAM
TRACER WIRES SPLICED TOGETHER REQUIRE WATERPROOF NUTS