Permit: T07PL01667

Parcel: 119040930


Addresses:

3618 S CLARK AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/26/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11/20/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CSA OR AGA SHUT OFF VALVE FOR STOVE
2. CALL BACK FOR INSPECTION (BEFORE 3:30 TODAY)
10/22/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 10/16/07 BEFORE CALLING FOR INSPECTION
10/16/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. SEE 313.3 2006 UPC ALL TRENCHES DEEPER THAN THE FOOTING OF ANY BLDG OR STRUCTURE AND PARALLELING THE SAME SHALL BE AT LEAST 45 DEG. THERE FROM
(12" DEEP FOOTING = 12" AWAY FROM FOOTING)
(24" DEEP FOOTING = 24" AWAY FROM BOTTOM EDGE OF FOOTING)

2. REMOVE TEE AT BLDG. SERVICE (TEST GAUGE) AND USE APPROVED 90 DEG. ELL
3. REQUIRE MINIMUM THREE POUND TEST

INSPECTION STOPPED
10/04/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. MINIMUM DEPTH FOR GAS PIPING IS 12" OF COVER
2. UNDERGROUND GAS PIPE TO BE SCOTCH-COAT
JOINTS AND MARRED PIPE TO BE PRIMED
JOINTS AND MARRED PIPE TO BE TAPED
3. MAY NOT TRENCH NEXT TO FOOTING
4. FLEX MAY NOT PASS THRU WALL OR PARTITION
5. ALL VALVES TO BE AGA OR CSA APPROVED.