Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2007 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 11/20/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE CSA OR AGA SHUT OFF VALVE FOR STOVE 2. CALL BACK FOR INSPECTION (BEFORE 3:30 TODAY) |
|
| 10/22/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* COMPLETE LIST FROM 10/16/07 BEFORE CALLING FOR INSPECTION |
|
| 10/16/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. SEE 313.3 2006 UPC ALL TRENCHES DEEPER THAN THE FOOTING OF ANY BLDG OR STRUCTURE AND PARALLELING THE SAME SHALL BE AT LEAST 45 DEG. THERE FROM (12" DEEP FOOTING = 12" AWAY FROM FOOTING) (24" DEEP FOOTING = 24" AWAY FROM BOTTOM EDGE OF FOOTING) 2. REMOVE TEE AT BLDG. SERVICE (TEST GAUGE) AND USE APPROVED 90 DEG. ELL 3. REQUIRE MINIMUM THREE POUND TEST INSPECTION STOPPED |
|
| 10/04/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. MINIMUM DEPTH FOR GAS PIPING IS 12" OF COVER 2. UNDERGROUND GAS PIPE TO BE SCOTCH-COAT JOINTS AND MARRED PIPE TO BE PRIMED JOINTS AND MARRED PIPE TO BE TAPED 3. MAY NOT TRENCH NEXT TO FOOTING 4. FLEX MAY NOT PASS THRU WALL OR PARTITION 5. ALL VALVES TO BE AGA OR CSA APPROVED. |