Permit: T07PL01582

Parcel: 136370070

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/13/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
OK FOR GAS
NEED P OF A FOR WH T&P TERMINATION
CLEARANCE GIVEN
RECALL FOR INSP
09/11/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE PERMIT FOR NEW WH
- PROVIDE PETITION OF APPEAL FORM FOR T&P TERM
INTO PAN
- SECURE VENT CONNECTION W/SCREWS
- PROVIDE CORRECT SIZE FLEX FOR 100,000 BTU FURN.
- PLUG DRAIN PAN.
- TERMINATE EXTERIOR RELIEF VALVE W/OUT THREADS.
- SHUT OFF VALVE REQUIRED AT HOUSE
- P.E REQUIRES 18" COVER
- PROVIDE AN AIR TEST
- INSTALL 1" PIPING TO FULL SIZED TEE AT WH/FURN SPLIT