Permit: T07PL01489

Parcel: 13326295B


Addresses:

533 N SARNOFF DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/19/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
09/12/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE T & P LINE TO BE SEPERATED. INSTALLED WYE FITTING WITH 1/8" BEND FOR TWO DRAINS ON 2" TAIL PIECE WITH 1" AIR GAPS ON EACH PIPE
2) REMOVE TAPE B-VENT DBL WALL TO CONNECTOR AT SINGLE WALL, ADD 3 SCREWS
3) INSULATE FLEX CONNECTOR AT FURNACE CABINET, SHOULD HAVE BEEN HARD PIPED OUTSIDE CABINET
4) A TRAP PRIMER WOULD BE IDEAL. YOU CAN DUMP H20 FROM T & P TO KEEP TRAP PRIMED