Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/12/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE T & P LINE TO BE SEPERATED. INSTALLED WYE FITTING WITH 1/8" BEND FOR TWO DRAINS ON 2" TAIL PIECE WITH 1" AIR GAPS ON EACH PIPE 2) REMOVE TAPE B-VENT DBL WALL TO CONNECTOR AT SINGLE WALL, ADD 3 SCREWS 3) INSULATE FLEX CONNECTOR AT FURNACE CABINET, SHOULD HAVE BEEN HARD PIPED OUTSIDE CABINET 4) A TRAP PRIMER WOULD BE IDEAL. YOU CAN DUMP H20 FROM T & P TO KEEP TRAP PRIMED |