Permit: T07PL01460

Parcel: 104091150


Addresses:

614 W CALLE ARIZONA

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/07/2007 PLUMBING - FINAL Not ready for Inspection 1. GAS REPIPE - TAPE MARRED PIPE, WHERE PROTECTIVE COATING HAS BEEN STRIPPED OFF
2. CAP OFF OR REMOVE OLD PIPING
3. FLEX CONNECTOR MAY NOT PASS THRU WALL OF APPLIANCE, HARD PIPE TO OUTSIDE FURNACE AND THEN ATTACH FLEX
4. REQUIRE 3 SHEETMETAL SCREWS AND EACH JOINT OF VENT CONNECTOR AT WATER HEATER
5. LEFT GAS CARD
SW GAS 889-1888