Permit: T07PL01448

Parcel: 117033570

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07PL01448

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK FOR GAS
UCC LEFT AT METER
08/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. YOU HAVE PROVIDED INSPECTION HISTORY
FOR GAS PACK OK
2. YOU HAVE PROVIDED AN APPROVED PLAN
3. NOTE #2 ABOVE ASKS FOR STD. TO ALLOW CSST TO BE RUN EXPOSED IN BASEMENT ALL THE WAY TO THE APPLIANCE YOU HAVE PROVIDED APPROVAL FOR CONCEALED FITTINGS AND PIPE.
08/20/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) INSTALLATION OF GAS PACK REQUIRES A PERMIT AND INSPECTIONS. PROVIDE APPROVAL FOR UNIT
2) PROVIDE INSTALLATION STD FOR CSST TO BE RUN EXPOSED IN BASEMENT
3) THIS IS NOT A RECONNECT: GAS PIPING HAS BEEN REPLACED WITH CSST. PROVIDE APPROVED PLAN SHOWING MATERIAL TYPE, LENGTH AND BTU CONSUMPTION
08/15/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. BAD GAUGE ON TEST SETUP FOR GAS PRESSURE TEST
2. PROVIDE PRESSURE TEST
3. PROVIDE INSPECTION HISTORY FOR GAS PACK IN BASEMENT