Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/20/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) YOU STILL HAVE SOME PIPE VISE JAW MARKS ON PIPING THAT NEED TO BE PRIMED AND WRAPPED 2) SHADE UNDER PIPING WITH CLEAN DIRT, NO CHUNKS 3) ELECTRICAL BONDING ALSO REQUIRED. YOU MAY BOND GAS PIPING TO WATER PIPING |
|
| 08/15/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - WRAP ALL TOOL MARKS BELOW GRADE - SUPPORT PIPING W/CLEAN DIRT - INSTALL SEDIMENT TRAPS - CORRECT VENT AT WH VENT CONNECTION TO FURNACE - ONCE TYPE B DOUBLE WALL IS INSTALLED YOU MAY NOT CHANGE BACK TO SINGLE WALL (SINGLE WALL IS OK TO USE INSIDE BUILDING) GAUGE 28 PSI ON GAUGE |