Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* OBTAIN AN ELECTRICAL PERMIT FOR NEW WIRING OR OBTAIN A COMBINATION PERMIT FOR A SINGLE FAMILY RESIDENCE. CORRECT VENT FROM FURNACE, USE LISTED FITTINGS AND SECURE, REMOVE GAS PIPING AT OLD WH LOCATION |
|
| 08/08/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE PERMITS FOR ALL WORK - THIS IS AN SFR THAT HAS BEEN COMPLETELY REMODELED - GAS WH HAS BEEN REPLACED WITH AN ELECTRIC WH - WH IS NO LONGER OUTSIDE BECAUSE PORCH HAS BEEN ENCLOSED - T&P MAY NOT TERMINATE INSIDE HOUSE - NEW ELECTRICAL WIRING HAS BEEN INSTALLED THROUGHOUT HOME - A NEW AC UNIT HAS BEEN INSTALLED - CONDENSATE MAY NOT TERMINATE ON ROOF - VENT PIPING AT FURNACE IS NOT PROPERLY INSTALLED - NEW PLUMBING FIXTURES ARE NOT PROPERLY INSTALLED |
|
| 08/07/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - POST ADDRESS - PROVIDE ACCESS - REPLACE DAMAGED PIPE SUPPORT ON ROOF - TERMINATE WH VENT ABOVE PARAPET - SECURE VENT CAPS - PROVIDE INSP HISTORY FOR NEW HEAT PUMP OR OBTAIN MECHANICAL PERMIT - LEAVE TEST ON SYSTEM. 30 PSI ON GAUGE. |