Permit: T07PL01369

Parcel: 134172650


Addresses:

7126 E 17TH PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/10/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
08/09/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT & SECURE GAS PIPING AT DROP TO WATER HEATER ON EXTERIOR AND AT WATER HEATER AND DRYER LOCATION
2. VENT FROM FURNACE TO BE EXTENDED TO 3' ABOVE TOP OF COOLER INTAKE WITH DOUBLE WALL VENT PIPING AND CAP WHEN WITHIN 10' OF INTAKE.
3. PROVIDE AGA OR CSA GAS SHUTOFF VALVE FOR DRYER
4. PROVIDE SEDIMENT TRAPS AT GAS ENTRY TO FURNACE AND WATER HEATER.