Permit: T07PL01368

Parcel: 131113630


Addresses:

2302 S JEFFERSON AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/03/2007 PLUMBING - GAS PRESSURE TEST Approved
08/02/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE 10 PSI TEST ON ENTIRE GAS SYSTEM
WITH NO PRESSURE LOSS FOR 15 MINUTES. USE TEST
GAUGE IN 1/10TH POUND INCREMENTS.
2. EXPOSE AREA OF REPAIR IF REPAIR HAS BEEN MADE FOR INSPECTION
3. PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES
4. PROVIDE BONDING OF BUILDING GAS PIPING
5. VENT FROM WATER HEATER TO BE DOUBLE WALL VENT PIPING LEAVING ENCLOSURE TO POINT OF APPROVED VENT CAP PROVIDE 3-GALV SCREWS AT EACH JOINT OF VENT PIPING
6. SHALL HAVE PIPE PENETRATING THRU WATER HEATER ENCLOSURE.
08/01/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*