Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/20/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PRESSURE TEST NOT HOLDING 2) COMPLETE LIST FROM 9/11/07 |
|
| 09/11/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED PERMITS FOR WH RELOCATE AND FURN FLASH ROOF PENETRATION INSTALL METALLIC PIPING IN EXTERIOR LOCATIONS B VENT REQUIRED ON EXTERIOR WH VENT USE BRACKET TO SECURE USE BRASS CAPS ON COPPER WATER LINES AT OLD WH LOCATION |
|
| 08/01/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/27/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WRAP ALL TOOL MARKS BELOW GRADE ON YARD PIPING 2. OBTAIN A MECHANICAL PERMIT FOR REINSTALLATION OF NEW COMBINATION UNIT 3. OBTAIN A PETITION OF APPEAL FORM FROM BUILDING OFFICAL FOR T&P TERMINATION INSIDE HOME IF UNABLE TO GRAVITY DRAIN OUTSIDE 4. COMPLY W/REQUIREMENTS OF PETITION OF APPEAL 5. 3/4 GAS SUPPLY IS NOT LARGE ENOUGH FOR NEW FURNACE SUPPLY FURNACE FROM 1" PIPE AT BUILDING SERVICE 6. REMOVE OLD PLUG VALVES 7. A BUILDING SHUT OFF VALVE IS REQUIRED 8. INSTALL LISTED ADAPTOR FOR 3" TO 6" VENT INCREASE 9. SECURE VENT CONNECTOR W/GALV SHEETMETAL SCREWS 10. PROVIDE A PRESSURE TEST WITH A 15 PSI GAUGE 11. PROVIDE ELECTRICAL BONDING IF RELOCATING WH OBTAIN A PERMIT FOR RELOCATING WH |