Permit: T07PL01353

Parcel: 126070070


Addresses:

3942 E 5TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/26/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
09/20/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PRESSURE TEST NOT HOLDING
2) COMPLETE LIST FROM 9/11/07
09/11/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED PERMITS FOR WH RELOCATE AND FURN
FLASH ROOF PENETRATION
INSTALL METALLIC PIPING IN EXTERIOR LOCATIONS
B VENT REQUIRED ON EXTERIOR WH VENT
USE BRACKET TO SECURE
USE BRASS CAPS ON COPPER WATER LINES AT OLD WH LOCATION
08/01/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/27/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WRAP ALL TOOL MARKS BELOW GRADE ON YARD PIPING
2. OBTAIN A MECHANICAL PERMIT FOR REINSTALLATION OF NEW COMBINATION UNIT
3. OBTAIN A PETITION OF APPEAL FORM FROM BUILDING OFFICAL FOR T&P TERMINATION INSIDE HOME IF UNABLE TO GRAVITY DRAIN OUTSIDE
4. COMPLY W/REQUIREMENTS OF PETITION OF APPEAL
5. 3/4 GAS SUPPLY IS NOT LARGE ENOUGH FOR NEW FURNACE
SUPPLY FURNACE FROM 1" PIPE AT BUILDING SERVICE
6. REMOVE OLD PLUG VALVES
7. A BUILDING SHUT OFF VALVE IS REQUIRED
8. INSTALL LISTED ADAPTOR FOR 3" TO 6" VENT INCREASE
9. SECURE VENT CONNECTOR W/GALV SHEETMETAL SCREWS
10. PROVIDE A PRESSURE TEST WITH A 15 PSI GAUGE
11. PROVIDE ELECTRICAL BONDING

IF RELOCATING WH OBTAIN A PERMIT FOR RELOCATING WH