Permit: T07PL01352

Parcel: 126170950


Addresses:

3939 E 17TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07PL01352

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2007 PLUMBING - FINAL Approved GAS CARD AT METER
08/08/2007 PLUMBING - FINAL Not ready for Inspection
08/03/2007 PLUMBING - FINAL Not ready for Inspection
07/31/2007 PLUMBING - FINAL Not ready for Inspection 1. VENT FROM FURNACE TO BE MADE UP CORRECTLY
WITH 3-GALV SCREWS AT ALL JOINTS OF ALL VENT PIPING AND TERMINATE 3' ABOVE TOP OF COOLER WHEN WITHIN 10' OF INTAKE WITH APPROVED VENT PIPING & CAP.
2. GAS PIPING IS REQUIRED TO BE BONDED (NOT GROUNDED ON EXTERIOR)
3. GAS PIPING TO BE CONFIGURED TO PROVIDE CLEARANCE FOR WATER HEATER/FURNACE.