Permit: T07PL01331

Parcel: 126100190


Addresses:

4422 E BRYN MAWR RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/01/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
07/30/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/26/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
NO ACCESS AT 9:21 UNABLE TO DO PM INSPECTION DUE TO WORK LOAD.
07/25/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE TEST AT TIME OF INSPECTION ON ENTIRE GAS SYSTEM WITH NO LOSS OF PRESSURE
2. ALL FITTINGS & TOOL MARKS TO BE PRIMED AND THEN 10MIL TAPED ON UNDERGROUND PIPING.
3. SHALL PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVES AND SEDIMENT TRAPS AT ALL APPLIANCES.
4. REMOVE TAPE FROM WYE FITTING ON VENT CONNECTOR IT SHALL BE FUNCTIONAL FITTING WITH NO REDUCTION IN SIZE FROM FURNACE VENT SIZE. ALL FITTINGS ON VENT PIPING TO HAVE 3-GALV SCREWS AT EACH JOINT. VENT PIPING THRU CEILING & ROOF TO BE FULLSIZE DOUBLE WALL TERMINATING 3' ABOVE COMBUSTION AIR INTAKE WITH APPROVED DOUBLE WALL VENT CAP.