Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/23/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SECURE GAS PIPING AT DROP TO FURNACE 2. PROVIDE CORRECT COMBUSTION AIR FOR WATER HEATER 30,000 BTU DEVICE 3. SECURE & SUPPORT ROOFTOP PIPING AT CORRECT INTERVALS 4. VENT FROM FURNACE TO BE 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' WITH DOUBLE WALL BENT PIPE & CAP. ALL JOINTS OF VENT PIPING TO HAVE 3-GALV SCREWS AT EACH JOINT. 5. PROVIDE BONDING OF BUILDING GAS PIPING 6. PROVIDE APPROVED AGA OR CSA GAS VALVE FOR STOVE |