Permit: T07PL01272

Parcel: 106120080


Addresses:

1455 W PRINCE RD


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T07PL01272

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/09/2007 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
10/05/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1. I'M GOING TO INSIST THAT ALL UNDERGROUND PIPING HAVE AT LEAST 12" OF COVER AT ALL POINTS
2. WIRE NUTS ARE TO WATERPROOF TYPE
09/12/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1. PIPING UNDER DRIVE IS COVERED WITH LESS
THAN 18" OF FILL
2. 12" OF COVER IS REQUIRED ELSEWHERE
REMOVE DEBRIS AND GARBAGE FROM TRENCH
EXPOSE ALL COVERED PIPE
3. LETTERING IS TO FACE UP
4. TRANSITION FITTINGS COVERED
5. BLUE TRACER WIRE IS REQUIRED
08/15/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PIPING UNDER DRIVE SHALL BE 18" DEEP
- 12" REQUIRED IN OTHER AREAS
- INSTALL W/PIPE MARKINGS FACING
- FE PVC FITTINGS NOT ALLOWED AT METALLIC CONNECTIONS
- USE PROPER ALIGNMENT AT ALL JOINTS
- TRACER WIRE REQUIRED
- USE BLUE, ATTACH AT 8' OC