Permit: T07PL01261

Parcel: 136350200


Addresses:

8425 E 24TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/23/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD AT METER
SW GAS 889-1888
07/20/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEST ON PIPING SHALL HOLD WITH NO LOSS OF PRESSURE
2. REMOVE COATING ON GAS PIPING AT BONDING LOCATION TO PROVIDE CORRECT BOND
3. VENT FROM WATER HEATER TO EXTEND 3' ABOVE TOP
OF COMBUSTION AIR INTAKE WITH DOUBLE WALL VENT
PIPING CAP