Permit: T07PL01199

Parcel: 137101540


Addresses:

5317 S CANADA DR

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/20/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1. PROVIDE DOUBLE WALL FLUE VENT AND CAP ON ROOF
2. CALL BACK FOR FINAL 03090
07/16/2007 PLUMBING - GAS PRESSURE TEST Cancelled IVRS - RI canceled
07/16/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. COMPLETE LIST #35, #6, #9 AND CALL FOR FINAL
2. PRESSURE TEST OK
07/12/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. UNCOVER ALL UNDERGROUND GAS PIPING FOR INSPECTION
2. PROVIDE PRIMER AND TAPE ON ALL TOOL MARKS AND FITTINGS
3. PROVIDE AGA APPROVED VALVES AND FLEXES ON WATER HEATER AND STOVE.
4. PROVIDE SUPPORT ON ALL GAS PIPING ABOVE GROUND
5. PROVIDE APPROVED FLUE VENT FOR WATER HEATER
6. EXTENDED FLUE VENT ON ROOF 3' ABOVE COOLER WITH DOUBLE WALL FLUE VENT AND CAP
7. PROVIDE NEW PRESSURE TEST
8. PROVIDE SEDIMENT TRAP AT WATER HEATER
9. PROVIDE ELECTRICAL BONDING FOR GAS PIPING