Permit: T07PL01180

Parcel: 11106395A


Addresses:

3319 E GLENN ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/19/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD AT METER
SW GAS 889-1888
07/17/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CALL IN PERMIT #T07PL01180 & #T07ME00524 AFTER HAVING CORRECT ADDRESS POSTED ON PERMIT ACTIVITY SHEET.
2. VENT FROM WATER HEATER TO COMPLY WITH NOTE #6 FROM 7/16/07
3. PLUG OLD GAS PIPING
4. STOVE PIPING TO BE COMPLETE TO AGA OR CSA GAS VALVE AND PROVIDE NEW GAS FLEX.
07/16/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
RETEST SYSTEM
1. PERMIT TO HAVE CORRECT ADDRESS LISTED AND STRUCTURE TO HAVE ADDRESS POSTED.
(THERE ARE (2) METERS & 2 RESIDENCES)
2. WALL HEATER IS LISTED APPROVED VENT FREE APPLIANCES
WHICH SHALL BE INSTALLED WITH APPROVED GAS VALVE AND FLEX.
3. TRACER WIRE TO BE INSTALLED ON YARD PIPING
4. AGA OR CSA APPROVED GAS VALVE & NEW FLEX TO BE INSTALLED FOR WATER HEATER
5. PROVIDE MINIMUM 100 SQ. INCHES UPPER & LOWER COMBUSTION AIR FOR WATER HEATER.
6. VENT FROM WATER HEATER TO BE IN CORRECT DIRECTION OF FLOW MINIMUM 1" ABOVE ROOF WITH DOUBLE WALL VENT MATERIAL THRU ROOF, APPROVED VENT CAP AND VENT PIPING TO HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES.