Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 07/23/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE LISTED TRANSITION FITTINGS ON B VENT EXTENSION OR USE LIKE MATERIALS 2. PROVIDE APPROVED VENT CAP ON B VENTS 3. PROVIDE A LISTED VENT TEE AT WH TO FURN CONNECTION 4. SEDIMENT TRAP REQUIRED ON GAS APPLIANCES 5. T&P MUST TERMINATE WITHOUT THREADS ABOVE GRADE OR PROVIDE PETITION OF APPEAL TO TERMINATE T&P INTO PAN AND INSTALL 125 PSI EXTERIOR RELIEF VALVE. |
|
| 07/20/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|