Permit: T07PL01122

Parcel: 121060840


Addresses:

5631 E MABEL ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07PL01122

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
07/19/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR TO PAY REFEE FOR NO WATER HEATER PERMIT
AS REQUESTED. NO FINAL INSPECTION UNTIL IT IS PAID.

CALL IN NEW WATER HEATER PERMIT
WITH THIS PERMIT FOR FINAL

12:48 NO ACCESS
07/18/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CITY SIGNED PETITION OF APPEAL SHALL BE ON SITE AS STATED ON 7/9/07

WATER HEATER SHALL BE ON SITE AS STATED ON 7/9/07
FAILURE TO COMPLY WILL RESULT IN DOUBLE FEES AND ADDITIONAL REFEES
07/11/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR TO PAY REFEE FOR NOT COMPLYING WITH ALL PAST NOTES ON THIS INSPECTION SHEET
NO FINAL UNTIL REFEE IS PAID AND PERMIT FOR WATER HEATER & PETITION OF APPEAL IS ON SITE.
07/09/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE PERMIT FOR NEW WATER HEATER
2. SHALL HAVE CITY SIGNED PETITION OF APPEAL FOR WATER HEATER ON SITE AND PROVIDE NIPPLE WITH NO THREADS ON DISCHARGE END OF 125# PRESSURE RELIEF DEVICE
NO GAS CARD REQUIRED.
PLEASE CALL IN THIS PERMIT FINAL AND WATER HEATER PERMIT FOR FINAL AFTER CORRECTION IS MADE.
07/02/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CORRECT COMBUSTION AIR FOR WATER HEATER
2. WATER HEATER TO HAVE FULL SIZE FUNCTIONAL TEMPERATURE & PRESSURE RELIEF GRAVITY DRAIN TO DAYLIGHT OR PROVIDE PETITION OF APPEAL ON SITE SIGNED BY CITY WITH CORRECT INSTALL.
3. VENT FROM WATER HEATER TO BE MADE UP CORRECTLY WITH 3-GALV SCREWS AT JOINTS, APPROVED VENT PIPING WITH APPROVED VENT CAP
4. PROVIDE BONDING OF BUILDING GAS PIPING SYSTEM
5. OLD GAS PIPING TO BE CAPPED AND OR REMOVED AFTER CHANGE OVER.