Permit: T07PL01113

Parcel: 123050710

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07PL01113

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD AT METER
07/03/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SHALL PROVIDE CORRECT VENT FOR FRONT BUILDING WATER HEATER/FURNACE THRU ROOF (DOUBLE WALL AND CEILING)
TERMINATING 3' ABOVE TOP OF AIR INTAKE WITH APPROVED DOUBLE WALL VENT CAP
07/02/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SEE NOTE #9 THIS SHEET AND PROVIDE FULLSIZE VENT PIPING AND APPROVED VENT CAP
06/29/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
OWNER CANCELLED
06/27/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE CITY APPROVED PLAN OF ACTUAL INSTALLATION WITH SIZING & SUB METER TO GUEST HOUSE
2. SHALL SEAL GAS ENTRY INTO BUILDINGS
3. BONDING SHALL BE TO BUILDING SIDE OF GAS PIPING
4. EXPOSE UNDERGROUND PIPING AT RISER LOCATIONS AND ALL NEW PIPING AS WELL AS EXISTING TO BE POTHOLED
RISERS SHALL BE PRIMED & THEN TAPED INCLUDING FITTINGS AND TOOL MARKS. UNDERGROUND PIPING SHALL BE FACTORY COATED PIPING.
5. PROVIDE 3-GALV SCREWS AT EACH JOINT OF FLUE VENT PIPING.
6. PROVIDE AGA OR CSA APPROVED GAS VALVES AT ALL APPLIANCE LOCATIONS
7. PROVIDE GRAVITY DRAIIN FOR WATER HEATER IN FRONT HOUSE
8. PROVIDE SEDIMENT TRAP AT WATER HEATER IN FRONT HOUSE
9. VENT FROM WATER HEATER FURNACE IN FRONT HOUSE TO BE EXTENDED UP WITH DOUBLE WALL VENT PIPING 3' ABOVE AIR INTAKES WHEN WITHIN 10' OF AIR INTAKE.