Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/20/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TEST SHALL HOLD WITH NO LOSS OF PRESSURE 2. PIPING TO BE IN PRACTICAL ALIGNMENT, USE FITTINGS TO MAKE CHANGES OF DIRECTION. 3. WATER HEATER REQUIRES T&P DRAIN PIPING GRAVITY DRAIN TO DAYLIGHT WITH 90 DEG. TERMINATION DOWN 4. ALL APPLIANCES REQUIRE AGA OR CSA APPROVED SHUT OFF VALVE 5. PROVIDE COMBUSTION AIR FOR WATER HEATER 6. PROVIDE BONDING OF BUILDING GAS PIPING 7. SHADE PIPING PROPERLY |