Permit: T07PL01061

Parcel: 136345300


Addresses:

3742 S PRUDENCE RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/24/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
06/15/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE BONDING OF BLDG GAS PIPING
2) VENTS FROM WATER HEATER AND FURNACE SHALL TERMINATE 3' ABOVE TOP OF COMBUSTION AIR INTAKE OR COLLER INTAKE WHEN WITHIN 10' OF INSTALLS WITH DBL WALL VENT PIPING (FULL SIZE) AND VENT CAP
3) SHALL PROVIDE SEDIMENT TRAPS ON GAS ENTRY TO WATER HEATER AND FURNACE
4) SHALL PROVIDE ROOF FLASHING ON PIPE PENETRATIONS THRU ROOF MADE WEATHER TIGHT
5) GAS PIPING AT METER TO BE SECURED AND SUPPORTED. GAS PIPING ON ROOF TO BE UP OFF ROOF ON SUPPORTS THAT ARE WEATHER RESISTANT AND SECURED TO PIPING AND TARED TO ROOF