Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T07PL00992
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/21/2007 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 06/12/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - B VENT IS UPSIDE DOWN - GAS FLEX CANNOT BE RE-USED - SEDIMENT TRAP REQUIRED - PROVIDE COMBUSTION AIR OPENINGS - PROVIDE MIN. 4" CLEARANCE TO COMBUSTIBLES IN FRONT PER WARNING LABEL - SHUT OFF VALVE REQUIRED ON WATER SUPPLY |