Permit: T07PL00990

Parcel: 133280040


Addresses:

8331 E 3RD ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/27/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
06/21/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. A LOW PRESSURE TEST REQUIRES A 15 PSI GAUGE
WITH 1/10 INCREMENTATIONS.
2. NEW WATER HEATER REQUIRES A PERMIT
3. TEMP & PRESSURE RELIEF VALVE CANNOT BE TRAPPED
4. PROVIDE A PETITION OF APPEAL FORM FROM BUILDING OFFICIAL FOR T&P TERMINATION INSIDE HOME IF UNABLE TO GRAVITY DRAIN.
5. A WATER HEATER PAN IS REQUIRED AND AN EXTERNAL #125 PSI RELIEF VALVE
6. A SEDIMENT TRAP ON GAS SUPPLY AT WH IS REQUIRED
7. SECURE VENT CONNECTOR W/GALV SHEETMETAL SCREWS NOT TAPE.
8. EXTEND FURNACE B VENT TO 3' ABOVE COOLER
06/12/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ACCESS TO GAS APPLIANCES
EXTEND B VENT TO 3' ABOVE COOLER
PRIME AND WRAP ALL TOOL MARKS BELOW GRADE
AND DO A NICER JOB WRAPPING FITTINGS
REMOVE ROCKS FROM PIPING
SHADE PIPING W/CLEAN FILL