Permit: T07PL00961

Parcel: 133397760


Addresses:

41 S GOLD MINE LP


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07PL00961

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
06/12/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ACCESS AT 2:20
06/11/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL BREAK OFF TAMPER SCREWS ON ALL VACUUM BREAKERS AT HOSE BIBBS.
2. SHALL SECURE SHUT OFF VALVES AT WASHER BOX AND HAVE HAMMER ARRESTORS INSTALLED CORRECTLY.

NOTE: IN THE FUTURE PLEASE LEAVE PAST INSPECTION HISTORY ON SITE.
06/08/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL SECURE ALL PEX AT APPROVED INTERVALS.
2. SHALL PROVIDE WATER HAMMER ARRESTORS FOR
HOT & COLD SUPPLY TO WASHING MACHINE.
3. SHALL PROVIDE 18" MINIMUM COPPER AT WATER HEATER PIPING IN WALL.
4. PROVIDE SEPARATION OF HOT & COLD TUBING.
5. PROVIDE VACUUM BREAKERS WITH TAMPER SCREWS BROKEN OFF AT ALL HOSE BIBS
6. PROVIDE CORRECT SUPPORT FOR REAR HOSE BIB
7. SHOWER VALVES REQUIRE BACKING AND SECURING TO BACKING.
8. SECURE ANGLE STOP AT MASTER STOOL AND KITCHEN SINK
06/05/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*