Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/30/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PETITION OF APPEAL #319.07 ON SITE 1. SHALL SECURE GAS PIPING AT WATER HEATER CLOSET. 2. PROVIDE 3-GALV SCREWS AT JOINTS OF WATER HEATER/FURNACE VENT PIPING. 3. PROVIDE DIELECTRIC BETWEEN COPPER & GALV FITTING AT WATER HEATER OR PROVIDE BRASS REDUCER IN PLACE OF GALV WHERE LEAK IS. |