Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/29/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. POST ADDRESS 2. NEW HBS REQUIRE VAC BREAKERS 3. PROVIDE PETITION OF APPEAL FOR WH T&P 4. EXTERIOR PRV SHALL BE #125 5. PROVIDE FLASHING AT ROOF PENETRATION, RETEST 6. PROVIDE 3 1/2" CLEARANCE ABOVE ROOF, SUPPORT PIPING 7. EXTEND B VENTS TO 3' ABV FORCED AIR INLET. |