Permit: T07PL00880

Parcel: 136120500


Addresses:

9542 E MYRA DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/11/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
14 PSI TEST PER APPROVED PLAN - GAS CARD AT METER
05/25/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE PIPE PRIMER THEN 10 MIL TAPE ALL UNDERGROUND FITTINGS & TOOL MARKS ON PIPING.
2. MAKE WEATHERPROOF FLASHINGS FOR PIPE PENETRATIONS THRU ROOF.
3. PROVIDE PROOF OF INSPECTION OF NEW AC UNIT ON EXISTING ROOF OR PROVIDE PERMIT FOR THIS WITH INSPECTION OF NEW AC/HEATING UNIT ON ROOF BY MECHANICAL INSPECTOR FOR GAS CLEARANCE CARD.
4. WATER HEATER VENT TO BE MINIMUM 3' ABOVE TOP OF COMBUSTION AIR INTAKE WITH DOUBLE WALL VENT PIPING AND CAP.
5. SHALL PROVIDE AGA OR CSA APPROVED GAS VALVES AT WATER HEATER.
6. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN SHALL GRAVITY DRAIN TO DAYLIGHT WITH FULL SIZE APPROVED PIPING MATERIAL NO FLEXES.
7. PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER VENT PIPING.