Permit: T07PL00867

Parcel: 133223130


Addresses:

138 N LANGLEY AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/25/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
05/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE PRESSURE TEST ON ALL GAS PIPING
2. EXTEND FLUE VENT 3' ABOVE COOLER
3. PROVIDE AGA VALVES
4. PROVIDE SEDIMENT TRAP FOR WATER HEATER & FURNACE
5. PROVIDE ELECTRICAL BONDING
6. PROVIDE APPROVED COUPLING FOR GAS PIPING FOR FURNACE.