Permit: T07PL00854

Parcel: 136053290

Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T07PL00854

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/22/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
15 PSI TEST FROM METER THRU EXISTING WITH REPAIR AT BUILDING SERVICE ENTRY TO WATER HEATER/FURNACE ONLY OK

SEE NOTE #1 & #4 AND COMPLY FROM 5/21/07 INSPECTION
CALL IN 03050 & 03090 FOR REINSPECTION
GAS CARD AT METER
05/21/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE #4 OR #6 BONDING WIRE WITH CLAMPS TO CLEAN AREA ON GAS PIPE & CLAMP ON COLD SIDE OF WATER PIPING.
2. GAS PIPING TO FIREPLACE IS REQUIRED TO BE SCOTCHCOATED WITH PRIMED & TAPED FITTINGS UNDERGROUND AND ABOVE GROUND PIPING SHALL BE 3 1/2 ABOVE FINISH GRADE WITH NO TRIPPING HAZARD. GAS VALVE IS REQUIRED TO BE OUTSIDE OF HEARTH WITHIN 6' OF HEARTH IN SAME ROOM AS FIREPLACE. NO LIVE GAS PIPING INTO FIREPLACE CLEANOUT TROUGH OR HEARTH BEFORE APPROVED GAS SHUT OFF VALVE.
3. TRANSITION FITTING FOR FURNACE VENT FROM SINGLE WALL TO DOUBLE WALL 4" X 5" TO BE MADE UP CORRECTLY.
4. VENT FROM FURNACE SHALL BE 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH DOUBLE WALL VENT PIPE & CAP.