Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PETITION OF APPEAL #362-07 COMPLETE DOUBLE WALL FROM EXISTING THRU TO POINT OF TERMINATION PER NOTE #4 FROM 6/11/07 INSPECTION |
|
| 09/20/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ONE HOME, UNABLE TO DO INSPECTION 9:10 AM |
|
| 08/14/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE LIST FROM 6/11/07 BEFORE CALLING FOR FINAL |
|
| 08/01/2007 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 07/25/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NO ONE HOME UNABLE TO DO INSPECTION 1:00 PM |
|
| 06/11/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAKE UP VENT CONNECTION AT SINGLE TO DOUBLE WALL CORRECTLY, PROVIDE 3-GALV SCREWS AT EACH JOINT OF VENT PIPING. 2. WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL GRAVITY DRAIN TO DAYLIGHT 3. PROVIDE CORRECT COMBUSTION AIR FOR 35,500 BTU DEVICE. 4. PROVIDE DOUBLE WALL VENT PIPING TO POINT OF TERMINATION AT CAP ON ROOF. |