Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SCOTCH COAT REQUIRES MINIMUM TWELVE INCHES OF COVER. 2. REMOVE APPLIANCE CONNECTOR AND HARDPIPE CONNECTION AT UNIT. 3. TEST ENTIRE SYSTEM - DO NOT TEST THRU APPLIANCES |
|
| 05/15/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. T&P RELIEF DRAIN TO BE APPROVED MATERIAL BLK. IRON PIPE NOT APPROVED FOR WATER T&P RELIEF DRAIN TO TERMINATE POINTING DOWN. 2. ALL OTHER CORRECTIONS MADE OK OK FOR GAS SW GAS 889-1888 |
|
| 05/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. IF THE GAS LINE WAS REPLACED, EXPOSE ALL OF THE GAS LINE FOR INSPECTION 2. REQUIRE SEDIMENT TRAPS AT WATER HEATER AND FURNACE 3. REQUIRE PROPER VENTING FOR FURNACE AND FOR WATER HEATER 4. REQUIRE BOND BETWEEN WATER AND GAS PIPING UNDERGROUND PIPING TO BE SCOTCH COAT PIPING MAY NOT BE INSTALLED UNDERGROUND UNDER ANY BLDG. |