Permit: T07PL00782

Parcel: 133088010

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/04/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/04/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
05/03/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL DUAL INLET WASHER BOX TO RECEIVE DISCHARGE FROM SOFTENER.
2. PROVIDE 1" AIR GAP.
3. PIPE TANK OVERFLOW TO EXTERIOR
4. REMOVE EXCESS FLUX FROM PIPING
5. REFER TO UPC INSTALLATION STANDARDS FOR COPPER TUBE INSTALLATION REQUIREMENTS.

REINSTALL CLEANOUT FITTINGS FOR WASHER, NEVER LEAVE OPEN SEWER PIPING. CLEANOUT SHALL BE WATER & GAS TIGHT.