Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/12/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL REVENT SANTEE CORRECTLY AND HAVE CLEANOUTS TO GRADE FOR FINAL |
|
| 06/08/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE NOTE #2, PROVIDE CORRECT FALL ON PIPING PROVIDE CORRECT INTERCEPTOR VENT INTERCEPTOR TANK TEST OK |
|
| 06/06/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL NEW PIPING TO BE TESTED 2. ALL PIPING TO HAVE MINIMUM 1/4" PER FOOT FALL 3. EXPOSE ALL PIPING FOR INSPECTION, PROVIDE BEDDING AND SHADING AS NEEDED 4. 4" DISCHARGE OF INTERCEPTOR CANNOT REDUCE TO 3" 5. PROVIDE TRACER WIRE ON NEW PIPING INSTALL |
|
| 06/05/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |