Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE OK OK FOR GAS UCC LEFT AT METER SW GAS 889-1888 |
|
| 04/27/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REDUCING FROM 1" TO 3/4" BEFORE A BRANCH TEE, ONLY DELIVERS 3/4" TO THE APPLIANCE. IF 1" IS REQUIRED THEN EXTEND THE ONE INCH ALL THE WAY TO THE FIRST BRANCH. 2. SEAL EXTERIOR WALL PENETRATION 3. INSTALL AVB'S ON HOSE BIBBS 4. PRESSURE RELIEF VALVE TO BE 6"-24" ABOVE GRADE AND TERMINATE IN A PLAIN END (NO THREADS ON THE OUTLET OF THE VALVE) 5. CONDENSATE PUMP MAY NOT BE IN THE PAN AND CERTAINLY NOT IN FRONT OF COMBUSTION CHAMBER 6. DRYER VALVE TO BE WITHIN 6' OF APPLIANCE TO BE APPROVED TYPE. TEST ENTIRE SYSTEM. |