Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07PL00714
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/02/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/01/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE MAX 135 DEG. CHANGE OF DIRECTION AT HAND SINK DRAIN ON HORIZONTAL DRAINAGE. 2. PROVIDE MINIMUM 1/4" PER FOOT FALL ON 3" GREASE TRAP INLET PIPING. PROVIDE VENT DOWNSTREAM OF GREASE TRAP PER PLAN WITH VENT FROM FLOW CONTROL TIED INTO VENT THRU ROOF. 3. PROVIDE GALV CAP AT OLD DRAINAGE BY WATER HEATER 4. PROVIDE FOAM WRAP THRU CONCRETE AT FLOOR LEVEL ON PIPING. |
|
| 04/24/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |