Permit: T07PL00705

Parcel: 13319042B


Addresses:

6765 E ROSEWOOD CI

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/15/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
04/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PETITION OF APPEAL ON SITE #295-07
1. PRESSURE RELIEF ON EXTERIOR TO BE 125 PSI TYPE
2. VENT FROM WATER HEATER & FURNACE TO BE INSTALLED WITH LARGER VENT DEVICE TYING IN AT LOWER LEVEL
THAN 3" VENTED DEVICE ABOVE FURNACE TIE IN. ALL JOINTS TO HAVE 3-GALV SCREWS ON VENT PIPING.
3. PROVIDE 1" MINIMUM CLEARANCE FROM COMBUSTIBLES (WIRES) FROM DOUBLE WALL VENT PIPING.
4. PROVIDE DOUBLE WALL VENT PIPING TO POINT OF TERMINATION 2' ABOVE COOLER INTAKE WITH APPROVED VENT CAP.
04/19/2007 PLUMBING - FINAL Cancelled CANCELLED PER CONTRACTOR MARCO #622-4782
04/19/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR