Permit: T07PL00700

Parcel: 133210890

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/20/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10 PSI TEST NEW PIPING FROM METER TO
WATER HEATER/FURNACE ONLY
04/19/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. GAS PIPING TO FIREPLACE SHALL BE TESTED THRU APPROVED GAS VALVE INTO HEARTH OF FIREPLACE. SHUT OFF VALVE SHALL IN SAME ROOM WITHIN 4' OF HEARTH OF FIREPLACE OR PIPING SHALL BE REMOVED FROM ENTIRE SYSTEM.
2. SHALL PROVIDE BONDING OF BUILDING GAS PIPING.

RETEST SYSTEM & CALL BACK IN FOR INSP.
04/18/2007 PLUMBING - GAS PRESSURE TEST Cancelled CANCELLED PER AMANDA OF APPERSON PLUMBING #623-8441
04/18/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection CANCELLED