Permit: T07PL00657

Parcel: 127120580


Addresses:

5616 E HOLMES ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/26/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/23/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
FROM METER THRU SYSTEM TEST OK
1. VENT FROM WATER HEATER & FURNACE TO BE FULL SIZE DOUBLE WALL THRU ROOF 2' ABOVE AIR INTAKES WITH APPROVED VENT CAP. PROVIDE 3-GALV SCREWS AT EACH JOINT OF VENT PIPING.
2. WATER HEATER TO HAVE FULL SIZE T&P DRAIN GRAVITY DRAIN TO DAYLIGHT OR PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE WITH CORRECT INSTALLATION FOR ALTERNATE FORM OF T&P RELIEF.
04/17/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1" PE YARD LINE OK IF SIZED PROPERLY
EXTEND 1" TO ABOVE GRADE
PROVIDE ACCESS TO ALL GAS APPLIANCES
PROVIDE TEST ON ENTIRE SYSTEM