Permit: T07PL00615

Parcel: 133502650

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07PL00615

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/13/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
04/12/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ELIMINATE 1" X 3/4" RESTRICTION AT WATER SERVICE.
2. SECURE TUBING IN WALL AT WASHER BOX
3. SECURE TUBING AT ANGLE STOPS IN ALL AREAS
4. LEAK UNDER KIT SINK
5. HOT WATER PIPING NOT SIZED TO MATCH ORIGINAL
EITHER MATCH ORIGINAL SIZING OR PROVIDE A CITY APPROVED PIPING DRAWING.
6. SEPARATE HW & CW TUBING TGHAT IS BUNDLED TOGETHER AND SUPPORT HORIZONTAL TUBING IN ATTIC PER CODE SPECIFICATIONS.