Permit: T07PL00595

Parcel: 115073320


Addresses:

1521 N 6TH AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/09/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/04/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
11.3 PSI DROP TO 9.5 -- CORRECT LEAK
OBTAIN PERMIT FOR NEW WH
SUPPORT HORIZONTAL PIPNIG W/PIPE SUPPORTS
CORRECT VENT AT WH, SECURE W/SCREWS
PROVIDE 3/4" PIPING OF APPROVED MATERIALS
BLK PIPE NOT ALLOWED FOR WATER
FULL PORT WATER VALVE REQUIRED
FLEX NOT ALLOWED ON T&P
T&P HAS LEAK
SEDIMENT TRAPS REQUIRED AT FURN & WH ON GAS SUPPLY
PROVIDE ELECTRICAL BONDING