Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* INSTALLED PER DELTA TWO REVISION OK TO COVER WATER TEST ONE RISER TO TEN FEET |
|
| 04/23/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | 1. NOT INSTALLED PER THE REVISED APPROVED PLAN 2. PLAN STILL SHOWS THE 2" SINK DRAIN CONNECTING TO THE BLDG. DRAIN YOU ARE STILL CONNECTED TO THE BLDG. SEWER REMOVE SANTEE AT EXTERIOR WALL AND USE PROPER DRAINAGE FITTINGS. |
|
| 04/17/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. PLAN CLEARLY SHOWS 2" WASTE CONNECTING TO EXISTING BLDG. DRAIN. YOU HAVE CONNECTED TO THE BLDG. SEWER AND RAN THE WASTE PIPING EXPOSED ON THE EXTERIOR WALL. YOU MUST PROVIDE THE LISTING FOR THE AAV TO BE INSTALLED IN AN EXPOSED EXTERIOR LOCATION 2. NOT INSTALLED PER PLAN NO REDLINES ON SITE |