Permit: T07PL00519

Parcel: 10611008E


Addresses:

3445 N ROMERO RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/02/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/28/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. SCOTCH-COAT PIPE REQUIRES MINIMUM TWELVE INCHES OF COVER AT ALL POINTS.
2. ALL MARRED SECTIONS OF PIPE TO BE TAPED
3. PIPE THRU MASONRY TO BE TAPED
EXTERIOR WALL PENETRATION TO BE SEALED.
4. SUPPORT UNDER FLOOR PIPING
5. CONNECT ALL PIPING
6. TEST ENTIRE SYSTEM
7. REQUIRE BOND BETWEEN GAS PIPE AND METALLIC WATER PIPE (OR GROUNDING ROD)
8. REQUIRE SEDIMENT TRAPS AT WATER HEATER AND FURNACE.
9. REQUIRE APPROVED VALVES
10. EACH APPLIANCE TO HAVE INDIVIDUAL SHUT OFFS
11. THIS MAY NOT BE A COMPLETE LIST