Permit: T07PL00516

Parcel: 135112520

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/10/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL HAVE RIDGID PIPING INTO (THRU) ENCLOSURE FOR GAS SUPPLY.
2. VENT TO BE DOUBLE WALL FROM EXIT OF ENCLOSURE TO TERMINATION MINIMUM 1' ABOVE ROOF WITH APPROVED DOUBLE WALL VENT CAP.
3. NO COMBUSTIBLE MATERIAL SHALL BE WITHIN 6" OF SINGLE WALL AND 1" OF DOUBLE WALL VENT PIPING.
4. SHALL PROVIDE 3-GALV SCREWS AT VENT PIPING JOINTS.
5. SECURE ENCLOSURE TO WALL OR PAD

NOTE: REMOVE THE TOWER FROM WITHIN 6" OF WATER HEATER PIPING, THIS IS A RISK FOR FIRE.