Permit: T07PL00494

Parcel: 133140610

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/21/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
03/19/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
P OF A 279-07

1. OK FOR GAS AFTER COMPLETING THE FOLLOWING CORRECTIONS, RECALL FINAL.
2. GAS FLEX AT FURNACE IS UNDERSIZED, INSTALL CORRECT SIZE.
3. SEDIMENT TRAP MINIMUM LENGTH IS 3"
SEDIMENT TRAP CANNOT TOUCH ROOF
INSTALL SEDIMENT TRAP AT FURNACE INLET.
4. SECURE PIPING FROM MOVEMENT AT FURNACE
5. USE NO TAPE AT VENT CONNECTION TO DOUBLE WALL AT WATER HEATER.
6. IS WATER PIPING METALLIC?
7. IT IS BETTER TO BOND TO GROUND AT ELECTRICAL METER
LOCATED NEXT TO GAS METER.