Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/19/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* P OF A 279-07 1. OK FOR GAS AFTER COMPLETING THE FOLLOWING CORRECTIONS, RECALL FINAL. 2. GAS FLEX AT FURNACE IS UNDERSIZED, INSTALL CORRECT SIZE. 3. SEDIMENT TRAP MINIMUM LENGTH IS 3" SEDIMENT TRAP CANNOT TOUCH ROOF INSTALL SEDIMENT TRAP AT FURNACE INLET. 4. SECURE PIPING FROM MOVEMENT AT FURNACE 5. USE NO TAPE AT VENT CONNECTION TO DOUBLE WALL AT WATER HEATER. 6. IS WATER PIPING METALLIC? 7. IT IS BETTER TO BOND TO GROUND AT ELECTRICAL METER LOCATED NEXT TO GAS METER. |