Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/15/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 6" CLEARANCE REQUIRED BETWEEN VENT CONNECTOR & COMBUSTIBLES. 2. SECURE EACH JOINT OF VENT CONNECTOR W/GALV SHEET METAL SCREWS. 3. FLEX NOT ACCEPTABLE ON T&P, T&P SHALL TERMINATE W/OUT THREADS. WH IS RELATIVELY NEW. 4. SUPPORT HORIZONTAL PIPING AT WH 5. INSTALL FLEX LARGE ENOUGH FOR 40,000 BTU WH |