Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/16/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1. ALL PIPING TO BE SECURED AT CORRECT INTERVALS. 2. VACUUM BREAKERS ARE REQUIRED AT ALL HOSE BIBBS WITH TAMPER SCREWS BROKEN OFF. 3. ALL ANGLE STOPS TO BE PROPERLY SECURED. 4. WATER HEATER TO HAVE 18" MINIMUM OF COPPER IN WALL 5. PROVIDE SEPARATION OF HOT & COLD TUBING. |