Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 04/26/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VENT PIPING TO BE MADE UP CORRECTLY AND HAVE 3-GALV SCREWS AT EACH JOINT. 2. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN SHALL BE RIGID FULLSIZE APPROVED PIPING GRAVITY DRAIN TO DAYLIGHT. 3. VENT FROM WATER HEATER TO TERMINATE MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE. |