Permit: T07PL00395

Parcel: 130100470


Addresses:

3150 E 23RD ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/16/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/09/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SCOTCH KOTE PIPE REQUIRED BELOW GRADE
PRIME THEN WRAP TOOL MARKS AND FITTINGS
PIPE SHALL HAVE 12" OF COVER AND BE CONTINUOUSLY SUPPORTED
RETEST SYSTEM

AT WATER HEATER
CORRECTLY INSTALL TEMPERATURE & PRESSURE RELIEF DRAIN. PIPE TO BUILDING EXTERIOR W/APPROVED MATERIALS. GRAVITY DRAIN AND TERMINATE 6" ABOVE GRADE SECURE VENT W/GALV SHEET METAL SCREWS
INSTALL SEDIMENT TRAP ON GAS SUPPLY
03/06/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. UNCOVER UNDERGROUND GAS PIPING AND PROVIDE PRIMER AND 10 MIL TAPE
2. TEST GAUGE SHALL HAVE 1/10 PSI INCREMENTATION.